A. In all areas of special flood hazards, the following provisions are required:

1. Anchoring.

a. All new construction and substantial improvements shall be anchored to prevent flotation, collapse, or lateral movement of the structure.

b. All manufactured homes must be anchored to prevent flotation, collapse or lateral movement, and shall be installed using methods and practices that minimize flood damage. Anchoring methods may include, but are not limited to, use of over-the-top or frame ties to ground anchors, and those listed in FEMA’s “Manufactured Home Installation in Flood Hazard Areas” guidebook. The anchoring requirement is in addition to applicable requirements for resisting wind forces.

2. Construction Materials and Methods.

a. All new construction and substantial improvements shall be constructed with materials and utility equipment resistant to flood damage.

b. All new construction and substantial improvements shall be constructed using methods and practices that minimize flood damage.

c. Electrical, heating, ventilation, plumbing, and air conditioning equipment and other service facilities shall be designed and/or otherwise elevated one foot or more above the base flood elevation.

3. Utilities.

a. All new and replacement water supply systems shall be designed to minimize or eliminate infiltration of floodwaters into the system.

b. Water wells shall be located outside of the floodway.

c. New and replacement sanitary sewage systems shall be designed to minimize or eliminate infiltration of floodwaters into the systems and discharge from the systems into floodwaters.

d. On-site waste disposal systems shall be located to avoid impairment to them or contamination from them during flooding.

4. Subdivision Proposals.

a. All subdivision proposals shall be consistent with the need to minimize flood damage.

b. All subdivision proposals shall have public utilities and facilities such as sewer, gas, electrical, and water systems located and constructed to minimize flood damage.

c. All subdivision proposals shall have adequate drainage provided to reduce exposure to flood damage.

d. Where base flood elevation data has not been provided or is not available from another authoritative source, it shall be generated for subdivision proposals and other proposed development which contain at least fifty lots or five acres (whichever is less).

5. Storage of Materials and Equipment.

a. The storage or processing of materials that could be injurious to human, animal, or plant life if released due to damage from flooding is prohibited in special flood hazard areas.

b. Storage of other material or equipment may be allowed if not subject to damage by floods and if firmly anchored to prevent flotation, or if readily removable from the area within the time available after flood warning.

6. Review of Building Permits. Where elevation data is not available either through the flood insurance study or from another authoritative source, applications for building permits shall be reviewed to assure that proposed construction will be reasonably safe from flooding. The test of reasonableness is a local judgment and includes use of historical data, high-water marks, photographs of past flooding, etc., where available. Failure to elevate at least two feet above grade in these zones may result in higher insurance rates.

B. In all areas of special flood hazards where base flood elevation data has been provided as set forth in MMC 14.01.050 or 14.01.120(B), the following provisions are required:

1. Residential Construction.

a. New construction and substantial improvement of any residential structure shall have the lowest floor, including basement, elevated one foot or more above base flood elevation. Mechanical equipment and utilities shall be waterproofed or elevated at least one foot above base flood elevation.

b. For all new construction and substantial improvements, fully enclosed areas below the lowest floor that are usable solely for parking of vehicles, building access or storage in an area other than a basement and that are subject to flooding shall be designed to automatically equalize hydrostatic flood forces on exterior walls by allowing for the entry and exit of floodwaters. Designs for meeting this requirement must either be certified by a registered professional engineer or architect or must meet or exceed the following minimum criteria:

i. Provide a minimum of two openings having a total net area of not less than one square inch for every square foot of enclosed area subject to flooding;

ii. The bottom of all openings shall be no higher than one foot above grade; and

iii. Openings may be equipped with screens, louvers, or other coverings or devices; provided, that they permit the automatic entry and exit of floodwaters.

iv. A garage attached to a residential structure, constructed with the garage floor slab below the BFE, must be designed to allow for the automatic entry and exit of floodwaters.

c. New construction and substantial improvements of any residential structure in an unnumbered A zone for which a BFE is not available and cannot be reasonably obtained shall be reasonably safe from flooding, but in all cases the lowest floor shall be at least two feet above the highest adjacent grade.

2. Nonresidential Construction. New construction and substantial improvement of any commercial, industrial or other nonresidential structure shall either have the lowest floor, including basement, elevated one foot or more above the level of the base flood elevation, or, together with attendant utility and sanitary facilities, shall:

a. Be dry floodproofed so that below one foot above the base flood level the structure is watertight with walls substantially impermeable to the passage of water;

b. Have structural components capable of resisting hydrostatic and hydrodynamic loads and effects of buoyancy;

c. Have a certification by a registered professional engineer or architect that the design and methods of construction are in accordance with accepted standards of practice for meeting provisions of this section based on their development and/or review of the structural design, specifications and plans. Such certifications shall be provided to the city engineer;

d. Nonresidential structures that are elevated, but not floodproofed, must meet the same standards for space below the lowest floor as described in subsection (B)(1) of this section;

e. Applicants floodproofing nonresidential buildings shall be notified that flood insurance premiums will be based on rates that are one foot below the floodproofed level (e.g., a building floodproofed to one foot above the base level will be rated as at the base flood level);

f. For all new construction and substantial improvements, fully enclosed areas below the lowest floor that are usable solely for parking of vehicles, building access or storage in an area other than a basement and which are subject to flooding shall be designed to automatically equalize hydrostatic flood forces on exterior walls by allowing for the entry and exit of floodwaters. Designs for meeting this requirement must either be certified by a registered professional engineer or architect or meet or exceed the following minimum criteria:

i. A minimum of two openings having a total net area of not less than one square inch for every square foot of enclosed area subject to flooding,

ii. The bottom of all openings shall be no higher than one foot above grade,

iii. Openings may be equipped with screens, louvers, or other coverings or devices; provided, that they permit the automatic entry and exit of floodwaters, and

iv. A garage attached to a residential structure, constructed with the garage floor slab below the BFE, must be designed to allow for the automatic entry and exit of floodwaters;

g. For all new construction and substantial improvement located in an unnumbered A zone for which a BFE is not available and cannot be reasonably obtained, the structure shall be reasonably safe from flooding, but in all cases the lowest floor shall be at least two feet above the highest adjacent grade.

3. Manufactured Homes.

a. All manufactured homes that are placed or substantially improved on sites that are:

i. Outside of a manufactured home park or subdivision;

ii. In a new manufactured home park or subdivision;

iii. In an expansion to an existing manufactured home park or subdivision; or

iv. In an existing manufactured home park or subdivision on which a manufactured home has incurred “substantial damage” as the result of a flood;

shall be elevated on a permanent foundation such that the lowest floor of the manufactured home is elevated to one foot or more above the base flood elevation and be securely anchored to an adequately anchored foundation system to resist flotation, collapse, and lateral movement.

b. All manufactured homes that are placed or substantially improved on sites in an existing manufactured home park or subdivision that are not subject to the provisions of subsection (B)(3)(a) of this section must be elevated so that the lowest floor of the manufactured home and associated mechanical equipment are elevated one foot or more above the base flood elevation.

4. Recreational Vehicles.

a. Recreational vehicles placed on sites are required to either:

i. Be on the site for fewer than one hundred eighty consecutive days;

ii. Be fully licensed and ready for highway use; or

iii. Meet the permit requirements of MMC 14.01.100 and the elevation and anchoring requirements for “manufactured homes” in subsection (B)(3) of this section.

b. A recreational vehicle is ready for highway use if it is on its wheels or jacking system, is attached to the site only by quick disconnect type utilities and security devices, and has no permanently attached additions.

5. Enclosed Area Below the Lowest Floor. If buildings or manufactured homes are constructed or substantially improved with fully enclosed areas below the lowest floor, the areas shall be used solely for parking of vehicles, building access or storage. (Ord. 019/2022 § 1; Ord. 004/2020 § 1(Exh. A); Ord. 018/2017 § 4; Ord. 004/2006 § 2; Ord. 021/2005 § 1)